Strømværdier i ampere for installationsmetoder i tabel B.52.1 – PVC-isolering/tre belastede ledere, kobber eller aluminium
| Nominelt leder-tværsnit mm² | Installationsmetode i tabel B.52.1 | ||||||
|---|---|---|---|---|---|---|---|
| A1 | A2 | B1 | B2 | C | D1 | D2 | |
| 1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 |
| Kobber | |||||||
| 1,5 | 13,5 | 13 | 15,5 | 15 | 17,5 | 18 | 19 |
| 2,5 | 18 | 17,5 | 21 | 20 | 24 | 24 | 24 |
| 4 | 24 | 23 | 28 | 27 | 32 | 30 | 33 |
| 6 | 31 | 29 | 36 | 34 | 41 | 38 | 41 |
| 10 | 42 | 39 | 50 | 46 | 57 | 50 | 54 |
| 16 | 56 | 52 | 68 | 62 | 76 | 64 | 70 |
| 25 | 73 | 68 | 89 | 80 | 96 | 82 | 92 |
| 35 | 89 | 83 | 110 | 99 | 119 | 98 | 110 |
| 50 | 108 | 99 | 134 | 118 | 144 | 116 | 130 |
| 70 | 136 | 125 | 171 | 149 | 184 | 143 | 162 |
| 95 | 164 | 150 | 207 | 179 | 223 | 169 | 193 |
| 120 | 188 | 172 | 239 | 206 | 259 | 192 | 220 |
| 150 | 216 | 196 | 262 | 225 | 299 | 217 | 246 |
| 185 | 245 | 223 | 296 | 255 | 341 | 243 | 278 |
| 240 | 286 | 261 | 346 | 297 | 403 | 280 | 320 |
| 300 | 328 | 298 | 394 | 339 | 464 | 316 | 359 |
| Aluminium | |||||||
| 2,5 | 14 | 13,5 | 16,5 | 15,5 | 18,5 | 18,5 | - |
| 4 | 18,5 | 17,5 | 22 | 21 | 25 | 24 | - |
| 6 | 24 | 23 | 28 | 27 | 32 | 30 | - |
| 10 | 32 | 31 | 39 | 36 | 44 | 39 | - |
| 16 | 43 | 41 | 53 | 48 | 59 | 50 | 53 |
| 25 | 57 | 53 | 70 | 62 | 73 | 64 | 69 |
| 35 | 70 | 65 | 86 | 77 | 90 | 77 | 83 |
| 50 | 84 | 78 | 104 | 92 | 110 | 91 | 99 |
| 70 | 107 | 98 | 133 | 116 | 140 | 112 | 122 |
| 95 | 129 | 118 | 161 | 139 | 170 | 132 | 148 |
| 120 | 149 | 135 | 186 | 160 | 197 | 150 | 169 |
| 150 | 170 | 155 | 204 | 176 | 227 | 169 | 189 |
| 185 | 194 | 176 | 230 | 199 | 259 | 190 | 214 |
| 240 | 227 | 207 | 269 | 232 | 305 | 218 | 250 |
| 300 | 261 | 237 | 306 | 265 | 351 | 247 | 282 |
NOTE 1: I kolonne 3, 5, 6, 7 og 8 er det antaget, at ledere er runde for tværsnit til og med 16 mm². Værdier for større tværsnit gælder for sektorformede ledere og kan med sikkerhed anvendes for runde ledere.