Tabel B.52.4

Strømværdier i ampere for installationsmetoder i tabel B.52.1 – PVC-isolering/tre belastede ledere, kobber eller aluminium

Nominelt leder-tværsnit mm² Installationsmetode i tabel B.52.1
A1 A2 B1 B2 C D1 D2
1 2 3 4 5 6 7 8
Kobber
1,513,51315,51517,51819
2,51817,52120242424
424232827323033
631293634413841
1042395046575054
1656526862766470
2573688980968292
3589831109911998110
5010899134118144116130
70136125171149184143162
95164150207179223169193
120188172239206259192220
150216196262225299217246
185245223296255341243278
240286261346297403280320
300328298394339464316359
Aluminium
2,51413,516,515,518,518,5-
418,517,522212524-
6242328273230-
10323139364439-
1643415348595053
2557537062736469
3570658677907783
508478104921109199
7010798133116140112122
95129118161139170132148
120149135186160197150169
150170155204176227169189
185194176230199259190214
240227207269232305218250
300261237306265351247282

NOTE 1: I kolonne 3, 5, 6, 7 og 8 er det antaget, at ledere er runde for tværsnit til og med 16 mm². Værdier for større tværsnit gælder for sektorformede ledere og kan med sikkerhed anvendes for runde ledere.